Explanation technical data
Selection boiler capacity
For the selection of the CH-boiler one can take the heating capacity in speed 6 at an
outlet temperature of 40 °C. If a CH-boiler is available, usually no extra extension is
needed, because more than 90 % of the heat produced by the air curtain benefits
the climate indoors.
Maximum heating capacity
For the maximum heating capacity in the tables on pages 12 - 15 the heating
capacity for each unit has been taken at speed 6 with an output temperature of 50 °C.
Water volume
The water volumes stated in the tables are based on a water temperature of 60/40 °C,
a room temperature of 20 °C and an outlet temperature of 40 °C. With different values
it is necessary to calculate the water volume with the formula below. With the help of
this formula it can also be determined which water volume is required to achieve the
necessary heating capacity at a given water volume or which maximum heating
capacity can be achieved with a certain water volume.
Water pressure loss
If different water temperatures than 60/40 °C are concerned, the water pressure
loss can be roughly calculated with the formula below. To do this the water volume
shouldfirstbecalculated(seeabove).
Sound
The sound data are based on the direct field, in a situation with an open door and a
sound absorbing ceiling. The sound data for different situations can be determined
by adding the adjacent values to the table values. Deviating distances and several
units next to each other can be calculated with the table below. Data of the 1 m unit,
measured on a distance of 3 m, are the basic assumptions. The factors apply to all
types of air curtains.
m
w
=watervolume[l/h]
Q
=heatingcapacity[kW]
(tablevalue)
ρ
w
=densityofwaterat90ºC
(=0.984)[kg/l]
c
pw
= specific heat of water
(=4.18)
ΔT
w
= temperaturedifferencewater[
°C
]
kJ
kgºC
m
w
=
•3600[ l/h]
Q
ρ
w
c
pw
ΔT
w
Δ p
w
1
= waterpressureloss
 (tablevalue)
Δ p
w
2
= waterpressureloss
m
w
1
= watervolume
(tablevalue)
m
w
2
= watervolume,calculated
 usingformula
Δ
p
w
2
=
Δ
p
w
1
•
m
w
1
(
m
w
2
)
2
Closeddoor: +1à2dB(A)
Acoustical“hard”ceiling: +2à3dB(A)
Correctionfactorsforsoundpressure
in dB(A)
Distance
Unit width (cm)
100 150 200 250 300 350
1.0 m +4.8 +6.2 +7.1 +7.6 +8.0 +8.3
2.0 m +1.8 +3.4 +4.5 +5.3 +6.0 +6.4
3.0 m 0 +1.7 +2.9 +3.8 +4.5 +5.0
4.0 m -2.5 -0.8 +0.4 +1.4 +2.1 +2.7
5.0 m -4.4 -2.7 -1.5 -0.5 +0.2 +0.8