Technical data CA
2
S/M/L/XL - 250
15
Basic data:
•doorwidth : 250cm
•roomtemperature : 20ºC
•airoutlettemperature
1
: speed1-5=35°C
speed6 =40°C
•powersupply :W=230V/E=400V
*Seetableonpage10.
CA
2
S-250
Water
Electric
door height*
weight model F/R/C
max. heating capacity
2
water flow rate
3
water pressure loss, incl. valve
3
max. power, motors
max.current,motors(1phase)
max. power consumption, heating
max.currentconsumption(3phases)
cm
kg
kW
l/h
kPa
kW
A
kW
A
200 - 240
102/138/130
28.9
767
8.89
0.47
2.12
-
-
108/144/136
24.8
-
-
0.47
2.12
26.1
39.8
Speed 1 2 3 4 5 6
air displacement
heating capacity
noise level at 3 m
m
3
/h
kW
dB(A)
1045
5.3
31
1465
7.3
39
1685
8.5
42
2185
11.0
47
2545
12.8
51
2880
19.3
54
CA
2
M-250
Water
Electric
door height*
weight model F/R/C
max. heating capacity
2
water flow rate
3
water pressure loss, incl. valve
3
max. power, motors
max.current,motors(1phase)
max. power consumption, heating
max.currentconsumption(3phases)
cm
kg
kW
l/h
kPa
kW
A
kW
A
220 - 280
114/150/142
39.6
951
13.14
0.67
3.1
-
-
120/156/148
33.1
-
-
0.67
3.1
34.8
56.5
Speed 1 2 3 4 5 6
air displacement
heating capacity
noise level at 3 m
m
3
/h
kW
dB(A)
1230
6.2
30
1825
9.2
40
2200
11.0
45
2985
15.0
51
3565
17.9
54
3940
26.4
57
CA
2
L-250
Water
Electric
door height*
weight model F/R/C
max. heating capacity
2
water flow rate
3
water pressure loss, incl. valve
3
max. power, motors
max.current,motors(1phase)
max. power consumption, heating
max.currentconsumption(3phases)
cm
kg
kW
l/h
kPa
kW
A
kW
A
250 - 330
154/197/191
82.4
1696
4.81
1.68
7.58
-
-
170/213/207
57.9
-
-
1.68
7.58
60.9
94.2
Speed 1 2 3 4 5 6
air displacement
heating capacity
noise level at 3 m
m
3
/h
kW
dB(A)
2860
14.4
41
3770
18.9
46
4720
23.7
50
6075
30.5
60
7160
35.9
56
8215
55.0
62
CA
2
XL-250
Water
Electric
door height*
weight model F/R/C
max. heating capacity
2
water flow rate
3
water pressure loss, incl. valve
3
max. power, motors
max.current,motors(1phase)
max. power consumption, heating
max.currentconsumption(3phases)
cm
kg
kW
l/h
kPa
kW
A
kW
A
300 - 380
163/206/200
99.9
1900
5.97
2.78
12.55
-
-
179/222/216
57.9
-
-
2.78
12.55
60.9
98.8
Speed 1 2 3 4 5 6
air displacement
heating capacity
noise level at 3 m
m
3
/h
kW
dB(A)
3425
17.2
47
4540
22.8
51
5735
28.8
55
7440
37.3
60
8830
44.3
64
9955
66.6
67
The CA
2
air curtain is as a standard suitable for all water ranges from 45/35 °C to 90/70°C.
1
Dependingonthesituationtheoutlettemperaturevariesinallspeedsbetween20°Cand50°Cmax.
2
Basedonalimitedairoutlettemperatureof50°C.
3
Basedonawaterrangeof60/40°C.