DF MANUAL INSTALLATION
Manual version 2.0 (26-10-2012) en-21
en
Master settings
Only if multiple units have been connected to a single
control panel
2.7.6 Multiple units operated from one control panel
• A maximum of eight units may be connected to a single
control panel.
• Units are daisy chained using Biddle control cables and
Connectors
E and G.
• The total length of the control cables between connected
units may not be any longer than 30 m.
• Configure any one unit as a master. The sequence of the
connected units is not important.
• Connect the control panel and external control compo-
nents to the master unit.
n Do NOT remove the external control input bridges
on the other units.
See also:
2.7.3 "External control input" on page 19
2.7.5 "Unit settings" on page 20
Units with two control PCBs
Only the following types: DF S-250-E, M-250-E,
L-250-E
These units have two control PCBs that each control a part of
the unit. The control PCB on the connection side has been
configured as master on delivery.
all units config-
ured as normal
units
one unit config-
ured as a master
unit
external control
input
only connected
unit responds
all units follow
the master
automatic tem-
perature control
each unit is
independently
controlled
all units are
controlled by
the master